Purpose
Alarm controller PS-1 is wall mounted multichannel controller which operate in conjunction with up to eight gas transmitter DG-1 to detect the presence of flammable gases and vapours in air or other transmitters with output analog signal from 4 to 20 mA, and digital indication at LCD of measuring meaning, light alarm and relay output at the exceeding of fixed thresholds. |
|
The description
The controller has provides:
- digital indication of measuring meaning in mA or % of lower explosion level (LEL) for detecting flammable gases and vapours concentration;
- two threshold of alarm action;
- the possibility to fix threshold of alarm action Threshold 1 and Threshold 2 for each channel of measuring;
- light alarm indication;
- relay outputs when measuring meaning exceeds the thresholds for each channel of measuring;
- operation and calibration of PS-1 bу the display menu.
The access to function of the display menu are carried out using the special electromagnetic key.
PS-1 can be connected to outer equipments using the interface RS485.
The controller is powered from 24 V dc supply.
On base of this controller, gas transmitters DG-1 and the transmitters of toxic gas concentration in air, for example, Polytron 2 XP Tox (Drager Safety AG & Co. KGaA, Germany) the flammable and toxic gas detection systems can be created.
|
Main technical data
Features
|
Meaning |
| Input/ the range of the measuring |
Analog 4 to 20 mA |
| The number of the measuring channels |
From 1 to 8 |
| The limit of the main error of the measuring of input signal, mA |
±0,3 |
| The range of fixing of thresholds of alarm action, mA |
4-20 |
| The limit of the main error of the alarm, mA |
±0,3 |
| The warm-up time, s, not more |
60 |
| The reaction time of alarm, s, not more |
7 |
| Power input, V |
Dc supply 24 V |
| Consumption power, VA, not more |
36 |
| Enclosure |
IP 20 |
| Size, mm, not more |
260х200х120 |
| Weight , kg, not more |
2,3 |
|
|
|
|
|