GAS DETECTION SYSTEMS SDK-2
|
Purpose
Gas detection systems SDK-2 are wall mounted multichannel controller wich operate in conjunction with up to eight explosion proof pellistor detector BS-1 to detect the presence of flammable gases and vapours in air, digital indication at LCD of measuring meaning, sound and light alarm at the exceeding of fixed thresholds. |
Main technical data
Features
|
Meaning |
| The nominal smallest digit of digital indication, % LEL. |
0,1 |
| The quantity of the digit of indication |
3 |
| The range of the measuring of flammable gas concentration in air,
% LEL
|
0-50 |
| The range of the indication of flammable gas concentration in air,
% LEL
|
0-60 |
| The limit of the main error of the measuring,
% LEL, not more
|
±5 |
| The range of fixing of thresholds of alarm action, % LEL |
0-50 |
| The limit of variation of measuring in air,
% LEL, not more
|
±2,5 |
| The warm-up time, s, not more |
120 |
| The response time, s, not more |
15 |
Enclosure:
- controller
- commutation module
- pellistor detector BS-1
|
IP 20
IP 20
IP 54
|
| Power input, V
|
220 (+22/-33)
|
| Consumption power, VA, not more |
25 |
Size, mm, not more
- singlechannel controller
- multichannel controller
- commutation module
- pellistor detector BS-1
|
160х90х60
210х150х90
270х175х105
140х140х135
|
Weight , kg, not more
- singlechannel controller
- multichannel controller
- commutation module
- pellistor detector BS-1
|
1,0
2,5
1,5
1,1
|
Attention: * - The controller switch off the power of sensor at exceeding gas concentration in air the meaning 60 % LEL for protecting sensor
|